  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 25
SECTION 5
TROUBLESHOOTING
DOCUMENT: 151315
PV-30208 Photovoltaic Inverter
Operation and Maintenance Manual
Copyright 2003, Xantrex Technology Inc.
5-2
FAULT DESCRIPTIONS AND TROUBLESHOOTING
noitpircseDtluaF)DCL(edoCtluaF
+AtluaFeciveDMPI1000x0
-AtluaFeciveDMPI2000x0
+BtluaFeciveDMPI4000x0
-BtluaFec
iveDMPI8000x0
+CtluaFeciveDMPI0100x0
-CtluaFeciveDMPI0200x0
egatloVrednUeniLCA0010x0
egatloVrevOeniLCA0020x0
yc
neuqerFrednUeniLCA0040x0
ycneuqerFrevOeniLCA0080x0
tluaFtnerruCdnuorG0008x0
egatloVrevOsuBCD0004x0
tluaFtesff
OTC00008
ecnalabmItnerruC000001
FAULT DESCRIPTIONS
(1) IPM Device Fault (0x0001 Through 0x0020)
Both over current and over temperature condition can cause IPM device faults. The fault code for both
conditions is the same for each device, while there is a unique fault code for each device.
Possible causes for over current condition:
Short circuit in output AC line.
Low supply voltage to IPM control circuit.
Shorted isolation transformer.
Possible causes for over temperature condition:
External cooling fan inoperable.
Airflow on heatsink impeded due to accumulation of debris.
Operation above rated ambient temperature for an extended period of time.
Auxiliary contact block on contactor K1 inoperable. This is only possible if the fan does not operate