Maintenance
3–4
3. Connect the positive battery cable from the inverter/charger to the
positive terminal on the battery; then the negative to the negative with
the last connection made at the Xantrex HD terminal to prevent
sparks. You may hear an audible “pop” and see a spark when you
make the last connection.
4. Tighten to a torque of 14.5 ft-lbs (+/-10%).
5. Check that the inverter is operating by enabling it from the toggle
switch as explained in “Using the toggle switch” on page 2–9.
Replacing the fuse
The inverter/charger over-current protection fuse, shown in Figure 1-1,
protects the unit from internal failure or reverse polarity when connecting
it to the battery. If it blows for any reason, replace it with only the fuse
types listed below.
Littelfuse Mega® Fast Blow, 250 A, 32 V; part number 298250
Bussmann® 250 A 48 V; part number AMG-250
To replace the fuse:
1. Lift the fuse cover off as shown in Figure 3-2.
2. Remove the spent fuse and install the new fuse.
Be sure to use a lock washer when replacing the nuts. Tighten to a
torque of 4-5.5 ft-lb (5.5-7.5 Nm).
WARNING: Explosion or Fire
Do not complete the next step if flammable fumes are
present. Explosion or fire may result. Thoroughly ventilate
the battery compartment before making this connection.
WARNING: Correct fuse type
To reduce the risk of fire and electrical hazards, replace the fuse
with a fuse of the same type and rating.
Using the wrong fuse type can damage the unit and void your
warranty.