Specifications
A–6 975-0288-01-01
10-amp Charging Profile
Table A-6 provides the specific charging parameters for the 10 Charging
Profile.
0-amp Charging Profile
When Charger Setting 0 A is selected, the Battery Charger is disabled and
will not charge the batteries. Use this mode if other DC charging sources
are available or if it is necessary to temporarily disconnect the AC
charging system.
Table A-6
10-amp Charging Profile
Parameter Name Default Value
Charger Setting 10 A
Maximum Bypass Current 1200 W (10 A)
Bulk Mode 10 A
Absorption Mode 14.2 Vdc (4 hours maximum)
Float Mode 13.7 Vdc (8 hours)
Switches from Absorption to
Float Mode
4 A
Switches from Float Mode
back to Bulk Mode within the
8-hour limit, if the Float
current increases to 6 A.
6 A
Standby Mode (Off Mode) 12.5 Vdc
Estimated charging time 32 hours based on a single battery box with
two 100 Ah, 12 Vdc batteries and no other DC
charging sources